33/11kV Oil-Immersed Power Transformer

Power Transformer Model: PP-PT-33/11-10MVA Standard: IEC 60076, BS 171, BNBC
⚡

PP-PT-33/11-10MVA

2.5 MVA - 20 MVA (ONAN/ONAF)

Quick Product Summary
  • Model: PP-PT-33/11-10MVA
  • Capacity: 2.5 MVA - 20 MVA (ONAN/ONAF)
  • Standard: IEC 60076, BS 171, BNBC
  • Manufacture: Positive Power Gazipur

Technical Sales Inquiry:

Direct Phone: +880 1712-345678
Email: info@positivepowerbd.com

Engineering Overview & Scope

Positive Power Bangladesh Ltd designs and manufactures heavy-duty 33/11kV oil-immersed power transformers tailored for primary utility substations, captive power plants, and large-scale industrial manufacturing complexes across Bangladesh.

Each unit is engineered with high-grade, cold-rolled grain-oriented (CRGO) magnetic silicon steel sheets with step-lap mitered core joints to minimize no-load losses and acoustic emissions. Windings utilize 99.9% high-conductivity electrolytic copper insulated with thermally upgraded kraft paper to guarantee exceptional mechanical withstand capability during external short-circuit transients.

Key Protective Features

  • Conservator tank design with dehydrating silica gel breather and magnetic oil level gauge (MOG).
  • Double-float Buchholz relay for early detection of internal winding insulation breakdown and oil gas accumulation.
  • Winding Temperature Indicator (WTI) and Oil Temperature Indicator (OTI) with dual alarm and trip micro-switches.
  • Spring-loaded Pressure Relief Device (PRD) with rapid micro-switch tripping.
  • Option for manual off-circuit tap changer (OCTC) or automatic on-load tap changer (OLTC).

Key Engineering Advantages

  • High-grade prime CRGO silicon core with step-lap mitered joints
  • 99.9% IACS high-conductivity copper conductor windings
  • Conservator tank with silica gel breather & magnetic oil level gauge
  • Double-float Buchholz relay protection & pressure relief valve
  • WTI and OTI temperature indicators with dual alarm/trip contacts
  • Option for Off-Circuit (OCTC) or On-Load Tap Changer (OLTC)

Primary Industrial Applications

  • ▪ 33/11 kV Utility Intake Grid Substations
  • ▪ Heavy Steel Re-Rolling Mills & Melting Plants
  • ▪ Textile Spinning & Denim Weaving Complexes
  • ▪ Cement, Fertilizer & Chemical Manufacturing Plants
Engineering Data

Comprehensive Technical Specifications

Manufactured and rigorously tested according to international IEC standards and certified by BUET (Bangladesh University of Engineering and Technology).

Technical Parameter Engineering Specification
Rated Capacity 2.5 MVA to 20 MVA (ONAN / ONAF)
Primary Rated Voltage 33 kV ± 2 x 2.5% (or OLTC ± 8 x 1.25%)
Secondary Rated Voltage 11 kV
Rated Frequency 50 Hz
Vector Group Dyn11 / YNd11
Type of Cooling ONAN (Natural) / ONAF (Forced Air)
Insulation Class Class A (Oil Immersed)
Basic Impulse Level (BIL) 170 kV (33kV) / 75 kV (11kV)
Temperature Rise Limit 50°C (Oil) / 55°C (Winding) at 45°C Ambient
Testing Standards Routine tested per IEC 60076 & BUET Certified

🔬 Routine & Type Testing

100% factory routine tests including Megger insulation, dielectric breakdown, turns ratio, load/no-load losses, and temperature rise per IEC 60076.

🏛️ BUET Tested & Endorsed

Independently verified and type-tested through Bangladesh University of Engineering and Technology (BUET) electrical testing laboratories.

🛡️ 18-Month Warranty & Support

Full warranty backing with 24/7 on-site emergency technical support, genuine OEM spare parts, and annual preventive maintenance contracts.

Fast Quote Request

Request a Quotation for 33/11kV Oil-Immersed Power Transformer

Please enter your project capacity requirements and site details below. Our senior power systems engineering team will provide a comprehensive technical and commercial proposal within 24 hours.

Request a Quote & Contact Form
Catalog Exploration

Related Equipment in Power Transformer

⚡
PP-PT-33/0.4-1600

33/0.415kV Step-Down Industrial Substation Transformer

Industrial step-down transformer transforming 33kV directly to 415V, eliminating intermediate 11kV equipment to optimize…

1000 kVA - 3150 kVA View Specs →